AWG Wire Gauge Converter
An AWG (Brown & Sharpe) gauge number n fixes a solid round conductor at 0.005 in × 92(36 − n)/39 in diameter, so 12 AWG measures 0.0808 in (2.05 mm) across, carries 6.53 kcmil (3.31 mm²) of metal, and runs about 1.588 Ω per 1,000 ft in annealed copper at 20 °C.
Choose any size from 4/0 down to 40, or switch to reverse mode and type a caliper reading to find the gauge. Add a conductor temperature and a run length to get the resistance you would actually install.

Engineering estimate, not a quote. Every figure describes an ideal bare, solid, round copper conductor; stranding, plating, insulation and the conductor specification called out on your drawing can all shift the real values.
How this works
A wire gauge number is an index, not a measurement. In the AWG (Brown & Sharpe) system the index hangs on two fixed diameters and one rule. NIST Handbook 100, Copper Wire Tables (1966 edition), sets No. 0000 at 0.4600 in and No. 36 at 0.0050 in, places 38 sizes between them in geometric progression, and describes the result as a gage "based upon a simple mathematical law." Because the law is exact, every row of a printed wire table can be rebuilt with a calculator, and that is all this converter does.
From size to index. Counting 1/0 as n = 0, 2/0 as −1, 3/0 as −2 and 4/0 as −3 puts every named size on one number line that is 39 steps long from −3 to 36. Wikipedia's AWG article uses the same convention. Each step multiplies the diameter by the 39th root of 92, which Handbook 100 gives as 1.122 932 2. Starting from 0.005 in at n = 36 and applying that ratio 36 − n times gives d = 0.005 in × 92(36 − n)/39. Millimeters follow from the inch, defined as exactly 25.4 mm in NIST SP 811, Appendix B.
From diameter to area. Conductor area is traditionally stated in circular mils: the diameter in thousandths of an inch, squared. A conductor 80.81 mils across has 80.81² ≈ 6,530 circular mils, or 6.530 kcmil. The unit leaves out the π/4 of the circle formula, so one circular mil is smaller than one square mil. NIST SP 811 converts one circular mil to 5.067 075 × 10⁻¹⁰ m², so multiplying kcmil by 0.5067075 gives mm².
From area to resistance. Handbook 100 records the International Annealed Copper Standard, adopted by the International Electrotechnical Commission in 1913, as 0.017 241 Ω·mm²/m at 20 °C. In conductivity terms that is exactly 58 m/(Ω·mm²), so the converter uses 1/58. Resistance per meter is that resistivity divided by area in mm². For 12 AWG: (1/58) ÷ 3.3088 = 0.005 211 Ω/m, which is 5.211 Ω/km or 1.588 Ω per 1,000 ft, the same pair Wikipedia lists for 12 AWG solid copper at 20 °C.
Temperature. Handbook 100 reports that the International Electrotechnical Commission fixed the temperature coefficient of standard copper at 0.00393 per °C at 20 °C, measured between points marked on a wire that is not restrained from expanding, and that its own tables assume a straight-line resistance curve up to 200 °C. The converter multiplies the 20 °C value by 1 + 0.00393 × (T − 20) and rejects any temperature outside 0 to 200 °C, the range those tables print.
Hard-drawn copper. Wire that is drawn without a final anneal conducts slightly less well. Handbook 100 found hard-drawn No. 12 about 2.7 percent below annealed wire and says that where a value has to be assumed, hard-drawn copper should be taken as 97.5 percent of the annealed standard, with a 20 °C coefficient of 0.00383. Selecting that option divides the annealed resistance by 0.975 and swaps the coefficient. Treat 97.5 percent as the handbook's averaging convention, not a measured property of the reel on your bench.
Reverse lookup. Solving the diameter formula for n gives n = 36 − 39 × log(d ÷ 0.005 in) ÷ log 92. The answer is a fractional index. The converter prints it, rounds it to the nearest whole size, and shows the sizes on either side with the percent difference, so you can see how good the match really is. With a strand count above 1, the measured strand is first turned into an equivalent solid diameter, d × √k, because the strands' areas add.
Worked example: a 50 ft run of 12 AWG, then an unmarked conductor
A control box on a drawing calls for a 50 ft lead of 12 AWG annealed copper, and the designer wants its resistance cold and at a 75 °C conductor temperature. A second, unlabeled solid conductor on the bench mics at 0.81 mm. Press Load the 12 AWG, 50 ft example and then Load the 0.81 mm sample to watch the converter reproduce each line below.
Two results matter here. The warm lead has about 22 percent more resistance than the room-temperature figure, so a voltage-drop check done only at 20 °C understates the loss in a conductor that runs hot. And the 0.81 mm sample lands within two hundredths of a step of 20 AWG, a clean identification; against 19 AWG or 21 AWG the same reading would be off by 11 to 12 percent in diameter, so the reading points to one size and only one.
Stranded conductors
Handbook 100 describes the common concentric-lay construction as a straight center wire wrapped in helical layers of 6, then 12, then 18 wires, and notes that makers usually start from the total cross section and work out the strand size from it. Wikipedia's AWG article states the gauge rule plainly: a stranded size is named for the summed strand areas, and "the gaps between strands are not counted," so the bundle comes out roughly 13 percent wider than solid wire of the same gauge. The simplest lay shows why. Seven strands that together equal a solid wire of diameter D each measure D ÷ √7 = 0.378 D, and three strand widths span the bundle, 3 ÷ √7 = 1.134 D. By our arithmetic the metal fills 7/9 of that bundle circle.
So a stranded size name is a rounded label, and here the copper actually exceeds solid 22 AWG. Handbook 100 adds that for stranding types other than concentric lay, at the same nominal cross-sectional area, "the data may differ by several percent," and that ASTM and IEEE specifications set a ceiling on how far a stranded conductor's resistance may exceed that of an equivalent solid conductor. Read the resistance output as the solid-wire baseline, and take the outside diameter of any stranded or insulated cable from its maker's data.
Where printed tables disagree, and why
Two careful sources can print slightly different numbers for the same size, and neither is wrong. Handbook 100 explains that the 1961 edition of ASTM B 258 rounded each calculated diameter to the nearest tenth of a mil for gages 0000 through 44, that those rounded figures served as the commercial gage diameters, and that every other table in the handbook was computed from them. Wikipedia's table appears, in our reading, to carry the unrounded formula value. At the heavy end the two agree. At 10 AWG, Handbook 100 prints 0.9988 Ω per 1,000 ft from 101.9 mils, while the unrounded 101.897 mils gives 0.9989. At 40 AWG the rounding is no longer cosmetic: the handbook's 3.1 mils sits 1.4 percent under the formula's 3.144 mils, which removes about 2.8 percent of the area. The converter therefore reports both the exact formula diameter and the 0.1-mil value, and computes area and resistance on each.
ASTM's public summary of the active edition, B258-18(2026), says the specification "prescribes the standard nominal diameters and cross-sectional areas" of these sizes and gives equations and rules for mass, length, resistance and breaking or rated strength. The current edition's tables sit behind a paywall and were not consulted, so this page makes no claim to reproduce them; where a contract cites B258, its own tables govern.
Common mistakes
- Reading the gauge scale as linear. 20 AWG is not half of 10 AWG. Ten sizes apart, the areas differ by a factor of 10.16 (10.38 kcmil against 1.022 kcmil), and the resistance by the same factor.
- Treating 1/0 as size 1. 1/0 is index 0, one full step heavier than 1 AWG (0.3249 in against 0.2893 in). Entering it as 1 understates the copper by about 21 percent.
- Borrowing a sheet metal chart. The Manufacturers' Standard Gauge for sheet steel rests on a weight basis, and its 16 gauge is 0.0598 in, while a 16 AWG conductor is 0.0508 in. In the gauge table of Wikipedia's sheet metal article, the aluminum column lines up with these wire numbers and the steel columns do not.
- Mixing kcmil with thousands of square mils. One kcmil is 0.5067 mm²; one thousand square mils is 0.6452 mm². Using the wrong one inflates area by 27 percent.
- Measuring over insulation, or across strands. The formula describes bare solid metal. Measure one strand, count the strands, and use the strand-count field.
- Ignoring loop length and temperature. A two-wire circuit has twice the run in its loop, and a hot conductor adds roughly 0.4 percent of resistance per degree above 20 °C.
Picking the right reference for the question
| Reference | Use it for | Where it stops |
|---|---|---|
| This converter | Gauge to diameter, area and resistance; checking a supplier's table; identifying an unmarked conductor | Bare solid round copper only; no insulation, ampacity or plating |
| Cable maker's datasheet | Outside diameter over strands and insulation, weight, strand build, voltage and temperature rating | Applies to that one product |
| Ampacity tables in the electrical code that governs the installation | How much current a conductor may carry in a given setting | Depends on insulation rating, bundling and ambient; not estimated here |
| Sheet metal gauge converter | Thickness of sheet steel, galvanized, stainless or aluminum called out by gauge | A different scale for steel; wire sizes do not carry over |
| Micrometer on the conductor | Incoming inspection and settling a disputed size | Measure bare metal at two angles; strip carefully so the conductor is not nicked |
Sources for the formula and constants
The two defining diameters, the 39th-root-of-92 ratio, the 0.1-mil commercial rounding, the International Annealed Copper Standard (0.017 241 Ω·mm²/m and 10.371 Ω·cmil/ft at 20 °C), the 0.00393 and 0.00383 temperature coefficients, the 97.5 percent hard-drawn assumption, the stranding description and the check values for No. 12 at 75 °C are from NIST Handbook 100, Copper Wire Tables (1966), Tables 1, 5 and 6. The closed-form diameter formula, the zero-size indexing, the stranded-wire rule and the 7-strand shortcut, and the 12 and 40 AWG comparison values are from the Wikipedia AWG article. The B258 scope wording is from ASTM's public B258 summary page. NIST SP 811, Appendix B.8 supplies the exact inch and foot and the circular mil conversion. The 16-gauge sheet steel thickness, its weight basis and the aluminum-column comparison are from Wikipedia's Sheet metal article. We fetched each of the five on November 20, 2026 and checked the converter's output against them that day.
Reviewed by the JCH tooling team · updated November 2026.
Wire gauge questions engineers ask us
What diameter and cross-sectional area is a given AWG?
Raise 92 to the power (36 minus the size) divided by 39, then multiply by five thousandths of an inch. For the aught sizes count below zero, so 2/0 is entered as minus one. Squaring that diameter expressed in mils yields the area in circular mils; divide by a thousand for kcmil, or multiply kcmil by 0.5067 for square millimeters. Some anchors: 4/0 is 0.46 in and 211.6 kcmil, 10 AWG about 0.102 in and 10.4 kcmil, 24 AWG about 0.0201 in and 0.404 kcmil.
How are 1/0, 2/0, 3/0 and 4/0 handled?
Each added zero is one more step past size 1 toward heavier wire. In index terms 1/0 is zero, 2/0 is minus one, 3/0 is minus two, and 4/0, the heaviest named size, is minus three, defined at 0.46 inch. People say one-aught through four-aught. Anything heavier than 4/0 is normally specified by its area in kcmil rather than by a gauge.
Why does going three sizes heavier double the copper area?
Three ratio steps widen the diameter by 92 to the 3/39 power, close to 1.416, and area scales with diameter squared, which makes about 2.005. Resistance per foot drops by the same factor. Ten steps give roughly 10.16 in area, the other mental shortcut wire tables lean on: every ten sizes, area and resistance move by about ten times.
How do I identify the gauge of an unmarked wire?
Strip a short piece, mic the bare metal at two angles ninety degrees apart and average them, then run the reverse lookup. If the index comes back within a tenth of a whole number, that size is a sound call by our rule of thumb. For stranded wire, count the strands and mic one of them instead of the bundle, because the spaces between strands make a bundle reading too large.
Does stranded 14 AWG have the same outside diameter as solid 14 AWG?
No. Stranded and solid wire of one gauge carry about the same metal area, but round strands cannot pack without voids, so the stranded conductor measures wider. Wikipedia puts the difference at roughly 13 percent; a seven-strand lay works out to 13.4 percent by geometry. Insulation adds more on top, so take the finished outside diameter from the cable maker.
How much does copper resistance rise when the wire runs hot?
For standard annealed copper, about 0.39 percent for every degree Celsius above 20 °C, applied linearly. At 75 °C that is a 21.6 percent increase over the 20 °C table figure, and at 90 °C about 27.5 percent. Hard-drawn wire uses a slightly smaller coefficient, 0.00383, on top of its higher starting resistance.
Can this converter tell me how much current a wire can carry?
No. Safe current depends on the insulation's temperature rating, how many conductors are bundled together, ambient conditions and the installation rules that apply, so it has to come from the ampacity tables of the governing electrical code or from the cable maker. What you get here is resistance, which you can use to estimate voltage drop and I²R heating once a size has been chosen.
Ask JCH about a conductor callout
Got a print that names a gauge but no strand build, or a cable exit to size in a molded housing? Type the question below and the site's AI assistant answers it in a chat panel at the lower right of this page.